QuietShield™ Hybrid
The Raymond EMC QuietShield™ Hybrid has a dual function. It delivers TEMPEST secure processing capability in addition to secure speech capability.
Request PricingFull turnkey solutions
Raymond EMC provides turnkey solutions that start with design and continue through to onsite installation and RF shielding effectiveness and STC certification. We also build in all electrical, HVAC, life-saving system and seismic requirements.
Versatile design capability
Raymond EMC’s modular system can be expanded or reduced to fit virtually any size requirement. Our smaller enclosures are free-standing, while our larger enclosures are tied to a parent room. We model your layout using SolidWorks 3D CAD software, which provides you with highly accurate drawings for approval.
Many of our options – such as vents, penetrations and even doors – are field locatable, meaning we can adjust their position onsite at no extra cost, and with no major design change.
RF shielding performance levels
RF shielding attenuation |
|
|
|
Magnetic fields |
20 dB at 1 kHz rising to 55 dB at 10 kHz and 95 dB at 200 kHz |
|
Electric fields |
100 dB from 200 kHz to 50 MHz |
|
Plane waves |
100 dB from 50 MHz to 1 GHz |
|
Microwaves |
100 dB at 10 GHz |
Acoustic attenuation |
|
|
|
Sound transfer coefficient |
> 52 |
Contact us for more information if your shielding requirements are not covered here.
Complete line of options
Clients work with our expert team to create custom solutions that can include:
- RF vestibules
- RF power line filters
- Internal electrical distribution
- RF signal filters
- Honeycomb waveguide air vents
- Bulkhead connector panels
- Copper screen panels
- Waveguide pipe penetrations
- Absorber and ferrite tile lining
- Functional finishes
Contact us for more options.
Compliance with industry standards
IEEE-STD-299 |
Standard method for measuring the effectiveness of electromagnetic shielding enclosures (2006) |
ITSG-02 |
Criteria for design, fabrication, supply, and installation and acceptance testing of walk-in, radio-frequency-shielded enclosures (1999) |
ASTM E90 |
Standard test method for laboratory measurement of airborne sound transmission loss of building partitions |
ASTM E336 |
Standard test method of sound transmission loss of building partitions |
ASTM E413 |
Classification for rating sound insulation |
Two-year warranty
All Raymond EMC QuietShield™ products come with a two-year limited warranty against defective materials and craftsmanship and to retain the specified RF shielding effectiveness.