Full turnkey solutions

Raymond EMC provides turnkey solutions that start with design and continue through to onsite installation and RF shielding effectiveness and STC certification. We also build in all electrical, HVAC, life-saving system and seismic requirements.

Versatile design capability

Raymond EMC’s modular system can be expanded or reduced to fit virtually any size requirement. Our smaller enclosures are free-standing, while our larger enclosures are tied to a parent room. We model your layout using SolidWorks 3D CAD software, which provides you with highly accurate drawings for approval.

Many of our options – such as vents, penetrations and even doors – are field locatable, meaning we can adjust their position onsite at no extra cost, and with no major design change.

RF shielding performance levels

RF shielding attenuation

Magnetic fields

20 dB at 1 kHz rising to 55 dB at 10 kHz

and 95 dB at 200 kHz

Electric fields

100 dB from 200 kHz to 50 MHz

Plane waves

100 dB from 50 MHz to 1 GHz

Microwaves

100 dB at 10 GHz

Acoustic attenuation

Sound transfer coefficient

> 52

Contact us for more information if your shielding requirements are not covered here.

Complete line of options

Clients work with our expert team to create custom solutions that can include:

  • RF vestibules
  • RF power line filters
  • Internal electrical distribution
  • RF signal filters
  • Honeycomb waveguide air vents
  • Bulkhead connector panels
  • Copper screen panels
  • Waveguide pipe penetrations
  • Absorber and ferrite tile lining
  • Functional finishes

Contact us for more options.

Compliance with industry standards

IEEE-STD-299

Standard method for measuring the effectiveness of electromagnetic shielding enclosures (2006)

ITSG-02

Criteria for design, fabrication, supply, and installation and acceptance testing of walk-in, radio-frequency-shielded enclosures (1999)

ASTM E90

Standard test method for laboratory measurement of airborne sound transmission loss of building partitions

ASTM E336

Standard test method of sound transmission loss of building partitions

ASTM E413

Classification for rating sound insulation

Two-year warranty

All Raymond EMC QuietShield™ products come with a two-year limited warranty against defective materials and craftsmanship and to retain the specified RF shielding effectiveness.